GEA BOCK EX-HG/HGX 88e SERIES
ATEX / IECEx Explosion-Protected Semi-Hermetic Compressor
The GEA Bock EX-HG/HGX 88e Series is a high-capacity, eight-cylinder, semi-hermetic reciprocating compressor range developed for industrial refrigeration and cooling applications in potentially explosive environments.
Designed for hazardous-area Zone 2 applications, the EX-HG/HGX 88e range incorporates explosion-protected electrical components, motor protection and special safety features.
The series offers large displacement capacities and is suitable for specialised refrigeration systems used in petrochemical facilities, oil and gas installations and industrial process cooling.
The catalogue range includes standard and stronger-motor versions, allowing selection according to operating conditions and cooling requirements.
AVAILABLE MODELS
Four EX-HG88e configurations are listed in the supplied catalogue, with two displacement sizes and standard or stronger-motor options.
EX-HG/HGX 88e/2735-4 3G
Eight-cylinder explosion-protected compressor with standard motor configuration.
EX-HG/HGX 88e/2735-4 S 3G
Stronger-motor version for applications requiring an extended motor capability.
EX-HG/HGX 88e/3235-4 3G
Higher-displacement eight-cylinder compressor for large industrial refrigeration installations.
EX-HG/HGX 88e/3235-4 S 3G
High-displacement compressor equipped with a stronger motor for demanding refrigeration applications.
PRODUCT FEATURES
ATEX Zone 2 Design
Explosion-protected compressor design for appropriately classified Zone 2 gas atmospheres, Category 3G.
Eight-Cylinder Configuration
High-capacity reciprocating compressor design suitable for large refrigeration and process cooling systems.
Explosion-Protected Terminal Box
Special terminal box and electrical protection design for hazardous-area operation.
Motor Winding Protection
PTC motor winding protection with associated electronic protection equipment.
Part-Winding Start
Motor design supports part-winding starting with a 50% / 50% winding ratio.
Optional Accessories
Suitable explosion-protected accessories may include oil sump heating and capacity regulation.
TECHNICAL SPECIFICATIONS
Technical data for the four EX-HG/HGX 88e compressor models listed in the supplied GEA Bock EX-HG catalogue.
| Specification | 2735-4 3G | 2735-4 S 3G | 3235-4 3G | 3235-4 S 3G |
|---|---|---|---|---|
| Compressor Type | Semi-Hermetic Reciprocating | |||
| Number of Cylinders | 8 | 8 | 8 | 8 |
| Displacement 50 Hz (m³/h) | 237.9 | 237.9 | 281.3 | 281.3 |
| Displacement 60 Hz (m³/h) | 285.5 | 285.5 | 337.6 | 337.6 |
| Power Supply 50 Hz | 380–420 V / 3 Phase / 50 Hz | |||
| Power Supply 60 Hz | 440–480 V / 3 Phase / 60 Hz | |||
| Motor Starting | Part-Winding Start | |||
| Maximum Working Current (A) | 114 | 135 | 131 | 160 |
| Maximum Power Consumption (kW) | 63.7 | 77.5 | 74.6 | 91.0 |
| Starting Current PW1 (A) | 475 | 520 | 475 | 520 |
| Starting Current PW1+2 (A) | 551 | 605 | 551 | 605 |
| Weight (kg) | 448 | 468 | 442 | 462 |
| Discharge Line DV | 54 mm (2 1/8'') | |||
| Suction Line SV | 76 mm (3 1/8'') | |||
| Oil Charge (L) | 9.0 | 9.0 | 9.0 | 9.0 |
| ATEX Category | Category 3G / Zone 2 | |||
| Temperature Class | T3 | |||
The values above follow the supplied GEA Bock EX-HG catalogue. Maximum power consumption values are specified for 50 Hz operation and are not refrigeration cooling capacities.
Specifications may differ in newer product revisions. Confirm final electrical, mechanical and certification data before ordering.
TYPICAL APPLICATIONS
Oil & Gas
Industrial refrigeration in appropriately classified hazardous-area installations.
Petrochemical Industry
Specialised cooling systems in facilities where flammable gases may be present.
Chemical Processing
Process cooling and refrigeration in suitable chemical production facilities.
Industrial Refrigeration
Large-capacity refrigeration systems requiring approved explosion-protected equipment.
Offshore Applications
Suitable cooling systems requiring hazardous-area protection and appropriate corrosion-resistant design.
Process Temperature Control
Industrial temperature-control systems in designated Zone 2 environments.
IMPORTANT ATEX SAFETY INFORMATION
The EX-HG/HGX 88e compressor series covered on this page is designed for ATEX Category 3G / Zone 2 applications. It must not be assumed suitable for Zone 1 installations.
Selection must be based on the exact compressor certification, gas group, temperature class, refrigerant, operating limits and hazardous-area classification.
The complete refrigeration installation, including electrical equipment, safety devices and accessories, must be assessed for compliance with applicable explosion-protection requirements.
GEA BOCK EX-HG/HGX 88e SERIES
HIGH-CAPACITY EXPLOSION-PROTECTED REFRIGERATION COMPRESSORS
Engineered for demanding industrial refrigeration and Zone 2 hazardous-area cooling applications.
LOOKING FOR A GEA BOCK EX-HG/HGX 88e?
Contact WORLD HVAC ENGRG. SDN. BHD. for GEA Bock EX-HG/HGX 88e compressor enquiries, model selection, quotations and technical assistance.
Please provide your preferred compressor model, refrigerant, electrical supply, required cooling conditions and hazardous-area classification.
SEND ENQUIRY